NEC® Text |
---|
210.8 Ground-Fault Circuit-Interrupter Protection for Personnel. Ground-fault circuit-interrupter protection for personnel shall be provided as required in 210.8(A) through (B) Other Than Dwelling Units. All Copyright© 2016 National Fire Protection Association |
Expert Analysis
Revisions in the 2017 NEC at 210.8(B) have resulted in the expansion of GFCI protection for non-dwelling unit receptacles to include all single-phase receptacles rated 150-volts to ground or less, 50-amperes or less; and three-phase receptacles rated 150-volts to ground or less, 100-amperes or less. These requirements have been expanded in recognition of the fact that shock hazards are not limited to 15- and 20-ampere, 125-volt receptacles alone at commercial/industrial applications. Receptacles of the higher voltage and current ratings in the locations identified in 210.8(B) present similar shock hazards as those of lower voltage and current ratings.